发布日期:2022-10-06 来源:bob集团运营部

摘 要:经由过程事情实践,先容了LW6-110型户交际流高压SF6断路器存于的家族性缺陷及其造成此缺陷的缘故原由举行了阐发会商,对于从业职员器重开关特征实验,避免开关变乱发生,提高断路器技能监视程度,有现实借鉴作用。

要害词:高压SF6断路器;同期;超程;速率

中图分类号:TK-9 文献标示码:A

Cause Analysis and Treatment Measures of the Defect of LW6-110 type SF6 Circuit Breaker

CAI An-quan

(State Grid Bazhong Power Supply Company, Bazhong 636000, Sichuan, China)

Abstract: Through the practice, introduces the familial defects of LW6110 type outdoor AC high-voltage SF6 circuit breaker, and its causes of the defects are analyzed and discussed. Pay attention to switching acteristics test of practitioners, prevent switch accidents, and improve technology supervision level of circuit breaker, are of practical reference.

Keywords: high-voltage SF6 circuit breaker; synonization; distance, speed

0 弁言

高压SF6断路器液压机构接纳的是航空油,基本上是不成压缩的,具备通报速率快、延时小、动作正确、输着力特征平稳、阻尼性好。但液压机构布局比力繁杂,元件及外接受路接头多,管路长,逝世角多,管路中空气很难经由过程高压放油阀排失,于逝世角处残留的空气会形成空气垫,对于液压机构动作特征影响很年夜。每一次年检预试中城市有几台开关特征实验分歧格,这类因断路器运行一段时间油路中存于空气,造成合闸速率降低,威逼着断路器以及体系安全运行,应引起高度器重[1]。

1 LW6-110型户交际流高压SF6断路器实验发明的问题

110kV文石线166开关使用的是江苏如皋高压电器厂出产的LW6-110型户交际流高压SF6断路器。2000年7月8日投产以来,每一次年检预试都发明该类断路器存于同期、合闸或者分闸时间、刚合或者刚分速率分歧格的安全隐患问题,首次测试接纳的断路器机械特征测试仪:成都多能电力LDCⅡ型开关特征测试仪。

原标题:LW6-110型SF6断路器缺陷研究